AIR POLLUTION — DISCHARGE OF SULPHUR DIOXIDE FROM PETROLEUM FACILITIES, O. Reg. 88/22
Section 19
Flares
Cite as AIR POLLUTION — DISCHARGE OF SULPHUR DIOXIDE FROM PETROLEUM FACILITIES, O. Reg. 88/22, s. 19 · current to November 11, 2026 · consolidated from February 25, 2022 · read from e-Laws on November 16, 2026
The text
(1) On and after July 1, 2024, a person shall not operate or cause or permit the operation of a flare at a petroleum facility unless the following performance criteria are met in respect of the flare:
1. A pilot flame must be present for at least 14 minutes in every 15-minute period when a substance is being conveyed to the flare.
2. There must be no more than five minutes of visible emissions from the flare in any two-hour period.
3. The flare tip velocity must be,
i. less than 18 metres per second, if the approved continuous monitoring plan for the facility indicates that the maximum allowable flare tip velocity will not be calculated, or
ii. if the approved continuous monitoring plan for the facility indicates that the maximum allowable flare tip velocity will be calculated, less than the lesser of,
A. 122 metres per second, and
B. the velocity determined in accordance with the following formula:
Log10 (A) = ( Σni=1 (B × C) + 1212) ÷ 850
in which,
“Σ” is the sum of the values in the enclosed expression for each component in the gas being conveyed to the flare, from i = 1 to i = n,
“A” is the maximum allowable flare tip velocity, expressed in feet per second,
“B” is the concentration of each component in the gas being conveyed to the flare, expressed as a volumetric fraction,
“C” is the net heating value of each component in the gas being conveyed to the flare, expressed as British Thermal Units per standard cubic foot,
“i” is an individual component in the gas being conveyed to the flare, and
“n” is the total number of components in the gas being conveyed to the flare.
4. The net heating value of the flare combustion zone gas must be at least 10 megajoules per cubic metre, averaged over a 15-minute period.
5. If the flare uses perimeter assist air, the net heating value dilution parameter must be at least 250 kilojoules per square metre, averaged over a 15-minute period.
(2) The averaging periods referred to in paragraphs 4 and 5 of subsection (1) are block averaging periods.
Read the AIR POLLUTION — DISCHARGE OF SULPHUR DIOXIDE FROM PETROLEUM FACILITIES on e-Laws ↗
Made under Environmental Protection Act, R.S.O. 1990, c. E.19.