SCHEDULE 2 ADDITIONAL REQUIREMENTS FOR CONTROLLED AREAS
The following are additional requirements for controlled areas under paragraph 7 of subsection 26 (1) of the Regulation:
Structure And Furnishings
1. The controlled area shall be constructed with smoke sealed floor to slab partitions or sealed partitions with gypsum board ceilings. Floor to ceiling partitions with any permeable material, including but not limited to acoustic tiles, shall not be used.
2. The controlled area shall be provided with a pressurized vestibule, having minimum dimensions of 1.8 metres in width and 2.4 metres in length, with two sets of doors with electric operators and door sweeps.
3. The controlled area shall not contain soft fabric window coverings, carpets, ceiling tiles or soft fabric cover furniture.
4. The furniture in the controlled area shall be of non-combustible, non-permeable, durable and easily cleanable surface material.
Ventilation
5. The controlled area shall be isolated from the other areas of the building and shall have a separate ventilation system that operates at all times. No air from the controlled area shall be circulated to the rest of the building.
6. The ventilation system shall provide separate and filtered supply air to the controlled area at a minimum ventilation rate of 30 litres per second per person for the maximum permitted occupancy of the controlled area. The ventilation system shall heat or cool the supply air to maintain the temperature conditions set out in paragraph 8.
7. The controlled area shall be maintained at a pressure that is at least five to seven Pascals less than the pressure in any adjoining area where smoking or the use of electronic cigarettes is prohibited. The rate of air exhausted from the controlled shall be at least 10 per cent greater than the rate at which air is supplied to the controlled area.
8. The controlled area shall be maintained at a temperature of at least 22°C and shall be increased, where appropriate, to a maximum of 25.5°C.
9. Thermal displacement ventilation shall supply the air at a low level close to the entrance of the controlled area at a maximum velocity of 0.20 metres per second.
10. The air from the controlled area shall be collected at ceiling level at the end of the area opposite the entrance and exhausted to the outside with a minimum velocity of 0.36 metres per second through each exhaust air discharge opening.
11. The exhaust air discharge openings for the air that is removed from the controlled area shall be located at least 3.6 metres above ground and six metres from any opening windows, balconies and air intakes.
12. Supply air intakes and exhaust air discharge openings shall be separated horizontally by a minimum of six metres.
13. All the equipment for the controlled area must be located in accessible locations. Switches and thermostats for the controlled area that are in public areas shall be provided with lockable cages that shall be kept locked, and to which only authorized persons have access.
14. All duct work shall be of rigid material. Balancing dampers shall be provided on all branch ducts.
15. The ventilation system shall be provided with an interlock between air supply and exhaust to ensure continuous operation of both systems.
16. The ventilation system shall incorporate a heat recovery system to capture the heat from the exhaust air flows.
17. The proper installation of the systems in the controlled area must be verified before the controlled area is used. All systems shall be balanced by a balancing contractor who is affiliated with the Associated Air Balance Council or National Environmental Balancing Bureau and who is not associated with the contractor who built the controlled area, the employer of the employees who maintain or clean the controlled area, or the proprietor of the controlled area.