fire code, O. Reg. 213/07
Section 9.9.4.5
Cite as fire code, O. Reg. 213/07, s. 9.9.4.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) In a building that is 4 or more storeys in building height or has a total area of 4000 m2 or more, an annunciator panel shall
(a) be installed near the main entrance, in the main reception area or other approved location that is readily accessible to the fire department, and
(b) indicate all floors with not more than one floor per zone indicated.
(2) Fire detectors required in Clauses 9.9.4.2.(2)(b) and (c) may be considered as part of the adjoining floor for the purposes of Clause (1)(b) of this Article.
Shutdown of air handling systems
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.