(1) Unless otherwise approved, manual pull stations shall be installed at (a) the main reception area, and (b) near every exit. (2) Despite Sentence (1), a manual pull station may serve two exits where (a) the exits are not more than 9 m apart, (b) the exits are located on the same storey, and (c) the manual pull station is readily accessible and visible from each exit. (3) A manual pull station shall be (a) red in colour, (b) readily accessible and unobstructed, (c) readily visible, and (d) unless otherwise approved, installed at a height not less than 1.2 m and not more than 1.5 m, measured vertically from the finished floor surface. Alarm signalling devices