fire code, O. Reg. 213/07

Section 9.9.3.3

Cite as fire code, O. Reg. 213/07, s. 9.9.3.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Each floor area shall be served by a minimum of two exits where (a) the floor area is intended for assembly occupancy, and (i) the distance of travel to an exit from any point in the space exceeds 15 m, or (ii) the occupant load exceeds 60 persons, (b) the floor area is intended for storage, and (i) exceeds 200 m2 in area, or (ii) the distance of travel to an exit from any point in the space exceeds 23 m, (c) the floor area is a basement, and (i) exceeds 200 m2 in area, or (ii) contains areas that are accessible to the public, or (d) the floor area is intended for a use other than that described in Clauses (a), (b) and (c), and (i) exceeds 100 m2 in area, or (ii) the occupant load exceeds 60 persons. (2) Despite Sentence (1), each floor area shall be served by at least two exits in buildings that are more than 3 storeys in building height. (3) Despite Sentence (1), where a building is 3 storeys in building height, the third storey shall be served by at least two exits unless approved alternative measures are used. (4) Despite Sentence (3), there may be a single exit from the third storey used solely as the residence of the hotel owner or manager. (5) The minimum distance between exits referred to in Sentences (1), (2) and (3) shall be 9 m or half the maximum diagonal dimension of the floor area, whichever is less. (6) Exits are deemed to comply with Sentence (5) if the floor area is divided by a fire separation having a fire-resistance rating not less than 45 min so that it is necessary to pass through the fire separation to travel from one exit to another exit. Exit widths
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.