fire code, O. Reg. 213/07
Section 9.9.3.10
Cite as fire code, O. Reg. 213/07, s. 9.9.3.10 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Exit signs shall be installed in accordance with Subsection 3.4.5. of the 1994 Building Code.
(2) Each door opening into an exit stairway shall be identified with the number assigned to that floor in accordance with Article 3.4.6.17. of the 1994 Building Code.
(3) Existing doors that have the floor level identified in plain legible block letters or numbers at least 114 mm high with a 19 mm stroke on both sides of the door are deemed to be in compliance with Sentence (2).
Interior finishes
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.