fire code, O. Reg. 213/07
Section 9.9.2.15
Cite as fire code, O. Reg. 213/07, s. 9.9.2.15 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Buildings containing a hotel where the vertical distance between the floor of the top storey and grade exceeds 18 m shall have smoke control measures in conformance with Sentences (2) and (3).
(2) Buildings containing a hotel shall
(a) have smoke control measures that prevent smoke spread from floor areas containing other occupancies to upper floor areas that contain guest suites, or
(b) be sprinklered on all floor areas containing other occupancies that are located below floors that contain guest suites.
(3) Buildings containing a hotel shall have smoke control measures in conformance with Article 3.2.6.2. of the 1994 Building Code.
(4) A building is deemed to be in compliance with Sentence (3) where
(a) all guest suites have access to an exterior balcony,
(b) the length of corridors serving guest suites does not exceed 30 m between exits,
(c) corridors serving guest suites are equipped with smoke detectors connected to the fire alarm system,
(d) corridors serving guest suites are subdivided in conformance with Sentence (5), or
(e) the building is sprinklered.
(5) The corridor subdivision referred to in Clause (4)(d) shall
(a) separate the corridor into at least two compartments by a fire separation that does not require a fire-resistance rating,
(b) be located so that not more than one of the required exit stairs is located in any one compartment and the distance of travel from any guest suite entrance door to an exit or adjacent compartment does not exceed 25 m, and
(c) include smoke-tight doors equipped with self-closing devices that act as closures in the fire separation.
Pipes, ducts and plenums
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.