fire code, O. Reg. 213/07
Section 9.9.2.12
Cite as fire code, O. Reg. 213/07, s. 9.9.2.12 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Fuel-fired appliances, except for cooking appliances, shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.
(2) Sentence (1) does not apply to a gas or oil-fired appliance installed on the roof of a building of noncombustible construction.
(3) Sentence (1) does not apply to fireplaces and space heaters provided the appliance is not located in an exit or in a corridor serving as an access to exit for guest suites.
(4) Despite Sentence (1), the fire-resistance rating of the fire separation above the room is not required where
(a) the required vertical fire separation to the room is provided, and
(b) the room area is sprinklered
(i) with a spacing not exceeding 9.5 m2 per sprinkler, and
(ii) so that a minimum average sprinkler discharge density of 6.5 L/min/m2 is provided over the room area.
(5) Where an appliance is separated in conformance with this Article, sufficient combustion air shall be brought directly from the outside for the safe operation of the appliance.
(6) If it is not practical to provide combustion air directly from the outside as required in Sentence (5), alternative means for the safe operation of the appliance may be approved.
(7) Despite Sentence (1), a fire separation is not required for a fuel-fired appliance located within a guest suite and serving only that guest suite.