fire code, O. Reg. 213/07

Section 9.8.4.1

Cite as fire code, O. Reg. 213/07, s. 9.8.4.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Interconnected smoke alarms required in Sentences 9.8.2.2.(2) and 9.8.3.3.(2) and Clause 9.8.3.4.(1)(b) shall be installed on or near the ceiling in each (a) storey within a residential unit, including every basement, and (b) shared means of escape. (2) Smoke alarms referred to in Sentence (1) shall be (a) interconnected so that the activation of any smoke alarm will sound a similar signal in each of the interconnected devices, (b) installed in accordance with the manufacturer’s instructions, and on floor levels containing bedrooms or sleeping areas, the required smoke alarms shall be installed between such bedrooms and the remainder of the residential unit, such as in a hallway or corridor serving such rooms or areas, (c) connected to an electrical circuit with no disconnect switch between the overcurrent device and the smoke alarms, (d) listed for use in an interconnected installation, and (e) audible in bedrooms when the intervening doors are closed. Smoke alarms
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.