fire code, O. Reg. 213/07
Section 9.6.5.4
Cite as fire code, O. Reg. 213/07, s. 9.6.5.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Hydrants shall be located within 90 m of the building face on which the principal entrance is located.
(2) A hydrant located within 45 m of a fire department connection, as required by Sentence 9.6.5.3.(1), is deemed to be in compliance with Sentence (1).
(3) Despite Sentence (1), existing hydrant locations that provide sufficient fire suppression capability in the circumstances and that are approved may be used.