(1) A voice communication system shall be provided where the vertical distance between the floor of the top storey and grade exceeds 36 m. (2) The voice communication system required by Sentence (1) shall (a) consist of loudspeakers operated from the central alarm and control facility or other location that is accessible to the fire department and supervisory staff required under Subsection 2.8.2. and that is approved, (b) provide a clear verbal signal throughout the building, except for within elevator cars, and (c) provide for automatic silencing of the fire alarm devices when the loudspeakers are in use. (3) Approved existing public address systems compatible with the fire safety plan required under Subsection 2.8.2. and capable of communicating instructions to the building occupants are deemed to be in compliance with Sentences (1) and (2). Emergency power