fire code, O. Reg. 213/07
Section 9.6.3.9
Cite as fire code, O. Reg. 213/07, s. 9.6.3.9 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Emergency lighting shall be provided in exit stairways, public corridors and other principal access to exits.
(2) Emergency lighting required in Sentence (1) shall be
(a) designed to provide illumination for a duration of at least
(i) 2 h in buildings whose highest floor level is more than 18 m above grade, and
(ii) 30 min in buildings whose highest floor level is not more than 18 m above grade,
(b) supplied by a source of energy separate from the primary electrical supply for the building, and
(c) designed to be automatically actuated when the power to the building is interrupted.
(3) Illumination from emergency lighting shall be an average of at least 10 lx at floor or tread level, or 1 watt/m2 of floor space.
Subsection 9.6.4. Fire Alarm and Detection
Fire alarm requirements
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.