fire code, O. Reg. 213/07

Section 9.6.2.5

Cite as fire code, O. Reg. 213/07, s. 9.6.2.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Each dwelling unit and sleeping room not within a dwelling unit shall be separated from adjacent rooms and areas by a fire separation having a fire-resistance rating not less than 45 min. (2) Public corridors shall be separated from adjacent rooms and areas by a fire separation having a fire-resistance rating not less than 45 min. (3) Existing fire separations having less than a 45 min fire-resistance rating are deemed to be in compliance with Sentences (1) and (2) where the floor area is sprinklered. (4) Existing fire separations having a fire-resistance rating not less than 30 min are deemed to comply with Sentences (1) and (2) if smoke detectors are installed in public corridors. Protection of openings in fire separations
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.