fire code, O. Reg. 213/07

Section 9.6.2.13

Cite as fire code, O. Reg. 213/07, s. 9.6.2.13 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Each room into which a linen or refuse chute discharges shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h. (2) Automatic sprinklers shall be installed in each linen or refuse chute (a) at the top, (b) at alternate floor levels, and (c) in the room or bin into which the chute discharges. (3) An existing chute installation is deemed to be in compliance with Sentence (2) where (a) the chute outlet in the discharge room is protected by an automatic, self-latching closure held open by a fusible link, (b) the room into which the chute discharges is sprinklered, and (c) at least one sprinkler head with a minimum discharge rate of 66 L/min is located at the top of the chute. Transformer vaults
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.