fire code, O. Reg. 213/07

Section 9.5.5.2

Cite as fire code, O. Reg. 213/07, s. 9.5.5.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) A standpipe and hose system in accordance with Articles 3.2.9.1. to 3.2.9.7. of the 1990 Building Code shall be installed in buildings more than 4 storeys in building height where the fifth or sixth storey is used for a residential occupancy. (2) A wet or dry standpipe system is deemed to be in compliance with Sentence (1) where it includes (a) a 50 mm riser and 50 mm extensions, (b) capped 38 mm hose valves located so that any point on the floor area may be reached by 30 m of hose plus 3 m of hose stream from at least one hose valve, (c) a fire department connection in accordance with Sentences 3.2.9.5.(2) to (9) of the 1990 Building Code, and (d) a water supply in accordance with Sentences 3.2.9.3.(1) to (3) of the 1990 Building Code. (3) Despite Sentences (1) and (2), existing standpipe systems and water supplies may be used if the systems or measures will provide sufficient fire suppression capability in the circumstances and if the systems or measures are approved. Sprinkler systems