fire code, O. Reg. 213/07

Section 9.5.4.4

Cite as fire code, O. Reg. 213/07, s. 9.5.4.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Interconnected smoke alarms required in Sentence 9.5.4.1.(2), Subclause 9.5.2.2.(3)(b)(i) or Clause 9.5.2.8.(5)(b) shall be (a) installed on or near the ceiling in public corridors of each floor area, adjacent to each stairway serving the public corridor and on or near the ceiling in the basement, adjacent to each stairway, (b) audible throughout the suites, (c) connected to an electrical circuit with no disconnect switch between the overcurrent device and the smoke alarms, and (d) listed for use in an interconnected installation. Smoke alarms
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.