fire code, O. Reg. 213/07
Section 9.5.4.1
Cite as fire code, O. Reg. 213/07, s. 9.5.4.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) A fire alarm system shall be installed in accordance with Articles 3.2.4.2. to 3.2.4.6., 3.2.4.8., 3.2.4.9. and 3.2.4.17. and Sentences 3.2.7.8.(1) to (4) of the 1990 Building Code, where
(a) the building is greater than 3 storeys in building height, or
(b) sleeping accommodation is provided for more than 10 persons.
(2) A building not greater than 3 storeys in building height that contains not more than 10 dwelling units and provides sleeping accommodation for not more than 24 persons is deemed to be in compliance with Sentence (1) where the building is equipped with
(a) smoke alarms in accordance with Article 9.5.4.4., installed and interconnected so that the actuation of any smoke alarm will sound a similar signal in each of the interconnected devices, and
(b) a manual pull station at each exterior exit door for the actuation of the smoke alarms in Clause (a).
(3) A building is deemed to be in compliance with Sentence (1) where
(a) each exit and public corridor is shared by not more than four dwelling units or not more than 10 persons in boarding, lodging, rooming or dormitory accommodation, or
(b) each dwelling unit and suite has direct access to outdoors by a door near ground level.
Non-electric fire alarm systems
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.