fire code, O. Reg. 213/07

Section 9.5.3.7

Cite as fire code, O. Reg. 213/07, s. 9.5.3.7 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Each fire escape used as an exit shall comply with Articles 3.4.7.2., 3.4.7.3., 3.4.7.5. and 3.4.7.6. of the 1990 Building Code. (2) If a fire escape serves any storey above the second floor, doorway openings and window openings shall be protected in accordance with Sentences (3) and (4) if located (a) within 3 m horizontally of any balcony, platform or stairway of the fire escape, (b) within 3 storeys below or 10 m below any balcony, platform or stairway of the fire escape, or (c) within 1.8 m above any balcony, platform or stairway of the fire escape. (3) Doorway openings referred to in Sentence (2) shall be protected with closures having a fire-protection rating not less than 20 min and equipped with self-closing devices. (4) Window openings referred to in Sentence (2) shall be protected with (a) closures having a fire-protection rating not less than 20 min and that are fixed shut or arranged to close automatically upon the operation of a fusible link, (b) wired glass screens set in fixed steel frames, (c) glass block, or (d) listed steel shutters arranged to close automatically upon the operation of a fusible link. (5) The fusible link referred to in Clauses (4)(a) and (d) shall comply with ULC-S505, “Standard for Fusible Links for Fire Protection Service”. (6) The wired glass screens and glass block referred to in Clauses (4)(b) and (c) shall be installed in accordance with Article 3.1.8.14. of the 1990 Building Code. Lighting
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.