fire code, O. Reg. 213/07

Section 9.5.3.5

Cite as fire code, O. Reg. 213/07, s. 9.5.3.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Each exit door, except for the main entrance to a building, dwelling unit or suite, shall have an exit sign when the exit serves (a) a building exceeding 2 storeys in building height, (b) a building having an occupant load greater than 150 persons, or (c) a floor area other than a single dwelling unit with a fire escape as part of a means of egress. (2) Where exit signs are not visible throughout the corridors and passageways, additional exit signs shall be installed in approved locations to indicate the direction of egress. (3) Exit signs required in Sentences (1) and (2) shall have (a) the word “EXIT” or the words “EXIT/SORTIE” in red letters on a contrasting background or white letters on a red background, (b) letters with strokes at least 19 mm wide, (c) letters at least 150 mm high when the signs are externally illuminated, and (d) letters at least 114 mm high when the signs are internally illuminated. Interior finishes
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.