fire code, O. Reg. 213/07

Section 9.5.2.6

Cite as fire code, O. Reg. 213/07, s. 9.5.2.6 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Fire separations having a fire-resistance rating not less than 1 h shall be provided between residential occupancies and other major occupancies. (2) Existing fire separations having a fire-resistance rating not less than 30 min are deemed to comply with Sentence (1) if (a) the building is sprinklered and the sprinkler system complies with Article 9.5.5.3., or (b) the part of the building containing the other major occupancy is equipped with heat detectors and connecting corridors are equipped with smoke detectors as part of the fire alarm system of the building. (3) Existing fire separations consisting of membranes of lath and plaster or gypsum board are deemed to be in compliance with Sentence (1). Fire separations between dwelling units and corridors
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.