fire code, O. Reg. 213/07

Section 9.5.2.2

Cite as fire code, O. Reg. 213/07, s. 9.5.2.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Buildings shall comply with the requirements of Sentence (2) where the building is (a) not more than 1 storey in building height and not greater than 1200 m2 in building area, (b) not more than 2 storeys in building height and not greater than 900 m2 in building area, or (c) not more than 3 storeys in building height and not greater than 600 m2 in building area. (2) Floor assemblies and walls, columns and arches supporting floor assemblies shall have a fire-resistance rating not less than 30 min. (3) Where sleeping accommodation, recreation rooms, meeting rooms or hobby rooms are not provided in the basement, an existing fire separation between the first storey and basement is deemed to be in compliance with Sentence (2) where (a) the basement is sprinklered, or (b) the building contains not more than four dwelling units and provides sleeping accommodation for not more than 10 persons, and (i) interconnected smoke alarms are installed in accordance with Article 9.5.4.4., (ii) doors connecting the basement and first storey are in compliance with Sentence 9.5.2.8.(4), and (iii) fire stopping of the wall space at the basement level is in accordance with Article 9.10.15.3. of the 1990 Building Code. (4) The water supply for the sprinklers referred to in Clause (3)(a) may be taken from the domestic supply where the supply provides sufficient density for the largest fire compartment and where the supply is approved. Deemed compliance
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.