fire code, O. Reg. 213/07

Section 9.5.2.14

Cite as fire code, O. Reg. 213/07, s. 9.5.2.14 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Each room into which a linen or refuse chute discharges shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h. (2) Automatic sprinklers shall be installed in each linen or refuse chute (a) at the top, (b) at alternate floor levels, and (c) in the room or bin into which the chute discharges. (3) Where the room into which the linen or refuse chute discharges is sprinklered and at least one sprinkler head is installed at the top of the chute, an existing chute installation is deemed to be in compliance with Sentence (2). (4) Despite Sentence 9.5.2.1.(1), a closure is not required at the opening between a linen or refuse chute and the room into which it discharges. Storage garages
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.