fire code, O. Reg. 213/07

Section 9.5.2.12

Cite as fire code, O. Reg. 213/07, s. 9.5.2.12 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Incinerator rooms and refuse storage rooms shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 45 min. (2) Refuse storage rooms shall be sprinklered (a) with a spacing that does not exceed 9.5 m2 per sprinkler, and (b) so that the sprinklers provide a minimum average density of 6.5 L/min/m2 over the refuse storage room area. Vertical service spaces