fire code, O. Reg. 213/07

Section 9.4.5.5

Cite as fire code, O. Reg. 213/07, s. 9.4.5.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Buildings containing a home described in Clause 9.4.1.1.(1)(a) or (b) that is a care occupancy or a care and treatment occupancy shall be sprinklered in conformance with Sentences (2) to (5) and the sprinkler system shall be installed (a) throughout the building, or (b) where the building is only partially occupied by the home, on those storeys of the building that are occupied by the home. (2) Except as permitted in Sentence (3), an automatic sprinkler system shall be installed in accordance with NFPA 13, “Standard for the Installation of Sprinkler Systems”. (3) In buildings not greater than 6 storeys in building height, sprinkler systems may be installed in accordance with NFPA 13R, “Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height”. (4) Sprinkler systems shall be equipped with local electric waterflow alarms. (5) If a fire pump is required by NFPA 13 or NFPA 13R, it shall be installed in accordance with NFPA 20, “Standard for the Installation of Stationary Pumps for Fire Protection”, if it has a rated net head pressure greater than 280 kPa. (6) Buildings described in Sentence (1) that are sprinklered in conformance with Article 9.4.5.2. on January 1, 2014 are deemed to be in compliance with Sentence (1). (7) Despite Clause (1)(b), installation of a sprinkler system is not required for those storeys containing a home where the home occupies no more than 10% of the floor area of the storey. SECTION 9.5 BUILDINGS UP TO AND INCLUDING 6 STOREYS IN BUILDING HEIGHT WITH RESIDENTIAL OCCUPANCIES Subsection 9.5.1. Application and General Application
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.