fire code, O. Reg. 213/07
Section 9.4.5.2
Cite as fire code, O. Reg. 213/07, s. 9.4.5.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Sprinkler systems shall be designed in conformance with Article 3.2.5.5. of the 1986 Building Code.
(2) Despite Sentence (1), water supply requirements for sprinkler systems required in this Section may be based on
(a) the operation of at least three sprinkler heads spaced not to exceed 14.4 m2 per head, and
(b) a sprinkler discharge rate of not less than 100 L/min at any single operating sprinkler head for a duration of 30 min.
(3) Despite Sentences (1) and (2), existing sprinkler systems providing adequate protection may be approved.
Firefighters’ elevators
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.