fire code, O. Reg. 213/07

Section 9.4.3.3

Cite as fire code, O. Reg. 213/07, s. 9.4.3.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Each exit stairway shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 45 min. (2) Closures in stairway fire separations shall conform to Article 9.4.2.8. Door swing