fire code, O. Reg. 213/07

Section 9.3.4.2

Cite as fire code, O. Reg. 213/07, s. 9.3.4.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) A fire alarm system complying with Articles 9.10.17.4., 9.10.17.5. and 9.10.17.11. of the 1986 Building Code shall be installed where (a) sleeping accommodation is provided for more than 10 persons, and (b) the floor assemblies have a fire-resistance rating not less than 45 min and public corridors or corridors serving sleeping rooms not within a dwelling unit are separated from the remainder of the building by fire separations having a fire-resistance rating not less than 30 min.
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.