(1) The flame-spread rating of interior wall and ceiling finishes within a means of egress shall not exceed 200.
(2) Despite Sentence (1), the flame-spread rating of interior wall and ceiling finishes of corridors and stairways shall not exceed 150.
(3) Doors within corridors and stairways referred to in Sentence (2) are permitted to have a flame-spread rating of up to 200.