fire code, O. Reg. 213/07

Section 9.2.5.2

Cite as fire code, O. Reg. 213/07, s. 9.2.5.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as permitted in Sentence (3), sprinkler systems shall comply with Article 3.2.5.5. of the 1986 Building Code. (2) An existing sprinkler system is deemed to be in compliance with Sentence (1) where the average sprinkler discharge density over the design area is at least equal to the minimum density corresponding to the area for the hazard classification as defined in Table 9.2.5.A. (3) Where buildings with a ceiling height in excess of 9 m are required to be sprinklered, the design of the system shall be approved prior to installation. (4) The water supply requirements for an existing sprinkler system shall be based on (a) the hazard classification, as determined in Table 9.2.5.A., and (b) the minimum sprinkler discharge density, area of application and sprinkler spacing, as determined in NFPA 13, “Standard for the Installation of Sprinkler Systems”, that corresponds to the hazard classification determined under Clause (a). (5) Clause (4)(b) does not apply to the water supply requirements for an existing sprinkler system in an arena or an exhibition hall. (6) The water supply requirements for an existing sprinkler system in an arena or an exhibition hall shall be based on the lesser area of (a) 100% of the display area, or (b) 280 m2. TABLE 9.2.5.A.
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.