fire code, O. Reg. 213/07
Section 9.2.3.4
Cite as fire code, O. Reg. 213/07, s. 9.2.3.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Each floor area shall be served by at least two exits.
(2) Despite Sentence (1), floor areas in buildings not exceeding 2 storeys in building height may be served by one exit where
(a) the occupant load for the floor area does not exceed 60 persons,
(b) the floor area does not exceed 200 m2, and
(c) the travel distance from any point on the floor area does not exceed 15 m.
Door swing
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.