fire code, O. Reg. 213/07

Section 9.2.3.2

Cite as fire code, O. Reg. 213/07, s. 9.2.3.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Where the occupant load of a room exceeds 60 persons, at least two egress doorways shall be provided in such a manner that one doorway can provide egress if the other doorway becomes inaccessible to the occupants. (2) An existing room with one doorway is deemed to be in compliance with Sentence (1) where (a) the occupant load does not exceed 100 persons, (b) the floor area is sprinklered and the sprinkler system complies with Article 9.2.5.2., and (c) the travel distance does not exceed 23 m. Access to exits