fire code, O. Reg. 213/07
Section 9.2.3.17
Cite as fire code, O. Reg. 213/07, s. 9.2.3.17 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Storage rooms, refuse storage rooms and laundry rooms that open directly into an exit stairway shall be sprinklered and separated from the exit stairway by a fire separation having a fire-resistance rating not less than 45 min.
(2) Other rooms that open directly into an exit stairway shall be separated from the exit stairway by a fire separation having a fire-resistance rating not less than 45 min.
(3) Despite Sentences (1) and (2), existing rooms opening directly into an exit stairway may be approved.