fire code, O. Reg. 213/07
Section 7.2.3.1
Cite as fire code, O. Reg. 213/07, s. 7.2.3.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Closures in vent openings into smoke shafts from each floor area shall be inspected sequentially over a period not to exceed five years.
(2) Every closure in an opening to the outdoors at the top of a smoke shaft shall be inspected annually to ensure that it will open
(a) manually from outside the building,
(b) on a signal from the smoke or heat actuated device in the smoke shaft, and
(c) when a closure in an opening between a floor area and the smoke shaft opens.
(3) In addition to the procedures described in Sentences (1) and (2), elevators in an elevator shaft that is intended for use as a smoke shaft shall be inspected semi-annually to ensure that on activation of the fire alarm system they will return to the street floor and remain inoperative.
(4) Where an air-handling system is used for venting floor areas in the event of a fire to comply with the requirements of the Building Code, the system shall be inspected annually to ensure that air is exhausted to the outdoors.
Subsection 7.2.4. Central Alarm and Control Facilities and Voice Communication Systems for Life Safety
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.