fire code, O. Reg. 213/07
Section 6.7.1.8
Cite as fire code, O. Reg. 213/07, s. 6.7.1.8 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as provided in Sentence (2) and (3), exit signs shall be inspected at intervals not greater than 12 months to ensure that the exit signs will be visible upon failure of the primary power supply.
(2) Exit signs provided with a battery back-up shall be inspected at intervals
(a) not greater than one month to ensure the exit signs will be visible upon failure of the primary power supply, and
(b) not greater than 12 months to ensure the exit signs will be visible for a duration equal to the design criterion upon failure of the primary power supply.
(3) Exit signs that contain self-luminous or photoluminescent material shall be maintained in accordance with
(a) the sign manufacturer’s maintenance instructions, if any, and
(b) the conditions outlined in the approval of the designated evaluation body under the Building Code, if any.