fire code, O. Reg. 213/07

Section 6.7.1.5

Cite as fire code, O. Reg. 213/07, s. 6.7.1.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Liquid fuel storage tanks shall be drained and refilled with fresh fuel at intervals not greater than 12 months. (2) The requirements of Sentence (1) may be achieved by replenishment as the result of the normal test program required in Article 6.7.1.1. Inspection of emergency lighting unit equipment
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.