fire code, O. Reg. 213/07

Section 6.7.1.1

Cite as fire code, O. Reg. 213/07, s. 6.7.1.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as provided in Sentence (2), and Articles 6.7.1.2. to 6.7.1.5., emergency power systems shall be inspected, tested and maintained in conformance with CSA-C282, “Emergency Electrical Power Supply for Buildings”. (2) An emergency electrical power supply system for emergency equipment in hospitals shall be inspected, tested and maintained in conformance with CSA-Z32, “Electrical Safety and Essential Electrical Systems in Health Care Facilities”. (3) If an emergency power system or any part thereof is shut down (a) the fire department and building occupants shall be notified in accordance with Article 1.1.1.1., and (b) the supervisory staff shall be notified. Instructions for switching and starting
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.