fire code, O. Reg. 213/07
Section 6.6.1.2
Cite as fire code, O. Reg. 213/07, s. 6.6.1.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as permitted in Sentences (2) and (3), valves controlling water supplies used exclusively for fire protection systems or combined domestic water supplies and fire protection systems shall be sealed in the open position and inspected weekly.
(2) Valves which are locked open or valves which are electrically supervised shall be inspected monthly.
(3) After any alterations or repairs, an inspection shall be made to ensure valves are returned to the fully open position and are sealed, locked or electrically supervised.
Ice accumulations