(1) Where sprinkler systems are installed, a supply of spare sprinkler heads and equipment shall be maintained in conformance with Sentences (2) to (5).
(2) Spare sprinkler heads shall be kept in a cabinet where the temperature does not exceed 38°C.
(3) The minimum stock of spare sprinkler heads to be kept on hand shall be
(a) 6 sprinkler heads for installations containing not more than 300 sprinklers,
(b) 12 sprinkler heads for installations containing from 301 to 1000 sprinklers, and
(c) 24 sprinkler heads for installations containing more than 1000 sprinklers.
(4) Spare sprinkler heads shall correspond to the types and temperature ratings of the sprinklers installed on the system.
(5) A wrench suitable for replacing sprinkler heads shall be kept in the cabinet where the spare sprinkler heads are stored.