fire code, O. Reg. 213/07
Section 6.5.5.4
Cite as fire code, O. Reg. 213/07, s. 6.5.5.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Dry-pipe valves shall be trip tested by means of the inspector’s test valve in accordance with Sentences (2) and (3) to ensure that they operate satisfactorily and that the sprinkler alarms are in operating condition.
(2) Dry-pipe valves shall be trip tested annually.
(3) During the test referred to in Sentence (2), the control valve is not required to be in the fully open position.
(4) Dry-pipe valves shall be trip tested at least once every three years with the control valve fully open.
(5) The trip time for the tests described in Sentences (2) and (4) may exceed the acceptance trip time by not more than 10%.
Water supply
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.