fire code, O. Reg. 213/07
Section 6.5.4.5
Cite as fire code, O. Reg. 213/07, s. 6.5.4.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Subject to Sentences (2) and (3), valves controlling sprinkler water supplies or alarms shall be sealed in the open position and inspected weekly.
(2) Valves which are locked open or valves which are electrically supervised shall be inspected monthly.
(3) After any alterations or repairs, valves shall be inspected to ensure they are in the fully open position and are sealed, locked or electrically supervised.
Subsection 6.5.5. Testing
Notification
Read the fire code on e-Laws ↗