fire code, O. Reg. 213/07
Section 6.5.2.2
Cite as fire code, O. Reg. 213/07, s. 6.5.2.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Sprinkler control valves and sprinkler water supplies shall not be shut down, disconnected or otherwise impaired for more than 24 h without notifying the Chief Fire Official.
(2) In buildings containing a hotel, sprinkler control valves and sprinkler water supplies shall not be shut down, disconnected or otherwise impaired
(a) for 24 h or less without notifying the Chief Fire Official in accordance with a schedule identified in the approved fire safety plan, or
(b) for more than 24 h without notifying the Chief Fire Official.
Schedule of temporary shutdowns
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.