fire code, O. Reg. 213/07

Section 6.4.3.2

Cite as fire code, O. Reg. 213/07, s. 6.4.3.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Standpipe system piping shall be hydrostatically tested for 2 hours at a pressure of not less than (a) 1400 kPa (gauge), or (b) 350 kPa (gauge) in excess of the normal hydrostatic pressure when the normal hydrostatic pressure is in excess of 1050 kPa (gauge). Fire department connections
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.