fire code, O. Reg. 213/07

Section 6.3.4.7

Cite as fire code, O. Reg. 213/07, s. 6.3.4.7 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) This Article applies to every building that contains a residential occupancy or a care occupancy where (a) the building contains (i) a fuel-burning appliance, (ii) a fireplace, or (iii) a storage garage, or (b) the residential occupancy or care occupancy is served by a forced-air fuel-burning appliance not contained within the building. (2) RESERVED (3) A carbon monoxide alarm shall be replaced within the time frame indicated in the manufacturer’s instructions. (4) Except as provided in Sentence (5), when a carbon monoxide alarm is replaced, the replacement carbon monoxide alarm (a) shall not provide a lower level or type of carbon monoxide protection than that required by the Building Code as it read on the day the building or part of the building was constructed, and (b) shall comply with CSA-6.19, “Residential Carbon Monoxide Alarming Devices” or UL 2034, “Single and Multiple Station Carbon Monoxide Alarms”. (5) When a carbon monoxide alarm that is required to be installed by Subsection 2.16.2. is replaced, the replacement carbon monoxide alarm shall conform to Article 2.16.2.1. (6) The Chief Fire Official may approve an alternative to a requirement of Sentence (4), or (5) if, in the opinion of the Chief Fire Official, the alternative provides life safety protection equivalent to or greater than the life safety protection that would be provided by the requirement. Testing
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.