fire code, O. Reg. 213/07
Section 6.3.3.8
Cite as fire code, O. Reg. 213/07, s. 6.3.3.8 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) This Article applies to rental suites.
(2) The landlord shall test smoke alarms annually and after every change in tenancy.
(3) The landlord shall test battery-operated smoke alarms after the battery is replaced.
(4) The landlord shall test smoke alarms that are connected to an electrical circuit after any change is made to the electrical circuit.
(5) For the purposes of Sentences (2), (3) and (4), smoke alarms shall be tested by activating the smoke alarm test feature.
(6) If the Building Code requires a visual signalling component that is integral with or connected to a smoke alarm, the landlord shall ensure that any test of the smoke alarm required by Sentences (2) to (4) activates the visible signalling component.