fire code, O. Reg. 213/07
Section 6.3.2.2
Cite as fire code, O. Reg. 213/07, s. 6.3.2.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as provided in Sentence (2), a fire alarm system, with or without voice communication capability, shall be inspected and tested in conformance with CAN/ULC-S536, “Standard for Inspection and Testing of Fire Alarm Systems”.
(2) Despite Clause 14.4.1.6. of CAN/ULC-S536, “Standard for Inspection and Testing of Fire Alarm Systems”, a UL listed smoke detector sensitivity instrument may be used to conduct annual sensitivity testing of smoke detectors.
(3) A description of the fire alarm system as required in CAN/ULC-S536, “Standard for Inspection and Testing of Fire Alarm Systems”, shall be kept current and maintained in the building at an approved location.
(4) A record of each device, component and circuit of the fire alarm system that is inspected and tested in accordance with Sentence (1) shall
(a) indicate whether the device, component or circuit is in proper working order, and
(b) be kept in accordance with Subsection 1.1.2.
(5) Where a fire alarm system is monitored to transmit a signal to the fire department, the owner shall record whether all signals from the tests conducted in Sentence (1), or other events, are received by the monitoring station, and records shall be kept in accordance with Subsection 1.1.2.
Central alarm and control facilities
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.