fire code, O. Reg. 213/07

Section 5.5.5.6

Cite as fire code, O. Reg. 213/07, s. 5.5.5.6 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Where perchloric acid is heated above normal ambient temperature, it shall be done in a separate power-ventilated enclosure (a) conforming to Articles 5.5.4.3. and 5.5.4.4., and (b) displaying conspicuously posted instructions specifying that the enclosure is to be used for this application only. (2) The power-ventilated enclosure required by Sentence (1) as well as its exhaust duct system shall be washed after each use to prevent the accumulation of highly unstable deposits. (3) Perchloric acid shall not be heated with an open flame or in a hot oil bath. Chemical wastes
Read the fire code on e-Laws ↗