The text

(1) Cylinders of dangerous goods classified as compressed gases shall not be located in laboratories unless (a) they are in use and connected (i) to a regulator to deliver gas, or (ii) to a manifold being used to deliver gas, or (b) one is serving as a single reserve cylinder for a cylinder described in Subclause (a)(i) to which it is firmly secured with a noncombustible attachment. (2) Storage cylinders and piping systems for dangerous goods classified as compressed gases used in a laboratory shall be firmly secured with a noncombustible attachment and protected against mechanical damage. (3) Each point of supply and each point of use of cylinders or piping systems for dangerous goods classified as compressed gases shall be provided with (a) a label identifying the gas being supplied, and (b) a manual shut-off valve. (4) Valves on cylinders for dangerous goods classified as compressed gases shall be closed when not in use. (5) Except as provided in Sentence (7), where cylinders of dangerous goods classified as toxic gases are used in a laboratory (a) they shall be located in a continuously mechanically ventilated gas storage cabinet, (b) all exhaust shall be directed to a treatment system designed to process the accidental release of gas, and (c) the gas levels in the air shall be monitored by a gas detection system designed to emit an audible and visual signal within the laboratory and at a central station when gas levels exceed the exposure limit values established by provincial or territorial regulations or municipal by-laws or, in the absence of such regulations or bylaws, when they exceed the exposure limit values stated in the Safety Data Sheet. (6) Except as permitted in Sentence (7), cylinders of dangerous goods classified as compressed gases of pyrophoric materials shall be located in a gas storage cabinet that is (a) continuously mechanically ventilated, and (b) sprinklered. (7) Where lecture bottles of dangerous goods classified as toxic gases or as compressed gases of pyrophoric materials are used in a laboratory (a) they shall be kept in a dedicated continuously mechanically ventilated hood or other continuously mechanically ventilated enclosure, and (b) all exhaust shall be directed to a treatment system designed to process the accidental release of gas. Refrigerated storage
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.