fire code, O. Reg. 213/07
Section 5.5.5.1
Cite as fire code, O. Reg. 213/07, s. 5.5.5.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) The quantity of dangerous goods kept in a laboratory shall be minimized and shall not exceed the lesser of
(a) the supply necessary for normal operation, or
(b) when located in
(i) a major occupancy that is classified as either an educational assembly occupancy or a business and personal services occupancy, 300 L of flammable liquids and combustible liquids, of which not more than 50 L shall be Class I liquids, or
(ii) a major occupancy that is classified as a care, care and treatment or detention occupancy, the quantities of flammable liquids and combustible liquids permitted in Sentence 4.2.6.3.(1).
(2) Quantities of flammable liquids and combustible liquids in excess of those permitted in Sentence (1) shall be stored in
(a) cabinets conforming to Subsection 4.2.10. except that, in laboratories described in Clause (1)(b), the total quantity of flammable liquids and combustible liquids stored in such cabinets shall not exceed the quantity permitted for one cabinet, or
(b) a room conforming to Subsection 4.2.9.
(3) Quantities of dangerous goods other than flammable liquids and combustible liquids in excess of those permitted in Sentence (1) shall be stored outside of the laboratory in conformance with Part 3.
Containers for flammable and combustible liquids
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.