(1) Belt conveyors and bucket elevator legs shall be equipped with safety devices to (a) detect excessive misalignment, blockage, slipping or slow-down of the conveying equipment, and (b) prevent conditions described in Clause (a) from creating a fire or explosion hazard by (i) alerting personnel trained in taking appropriate actions, or (ii) automatically stopping the conveying equipment. (2) Conveying equipment belts shall be made of static conductive materials to prevent buildup of static charges. (3) Conveying equipment bearings shall be (a) accessible for inspection and maintenance, (b) lubricated to prevent overheating, and (c) kept free of accumulation of combustible dusts. (4) Belt conveyor galleries and tunnels and bucket elevator leg enclosures shall be provided with explosion venting to the outdoors in conformance with Sentence 5.3.1.6.(2). Separators