fire code, O. Reg. 213/07

Section 5.3.1.4

Cite as fire code, O. Reg. 213/07, s. 5.3.1.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as provided in Sentence (2), a dust collector having a capacity greater than 2.36 m3/s shall (a) be located outside of a building, and (b) be equipped with explosion venting to the outdoors of not less than 0.1 m2 of vent area for each cubic metre of dust collector enclosure volume. (2) A dust collector described in Sentence (1) is permitted to be located inside a building if it is (a) provided with explosion venting to the outdoors as specified in Clause (1)(b), (b) equipped with an automatic explosion prevention system, or (c) located in a room (i) with fire separations having a fire-resistance rating of not less than 1 h, (ii) provided with explosion venting to the outdoors, and (iii) used solely for the housing of dust-collecting equipment. (3) When air exhausted by a dust collector described in this Article is returned to a building, the dust-collecting system shall be designed so that (a) returned air will not create an explosion hazard inside the building, and (b) the exhaust fan and ancillary equipment are automatically shut down in the event of a fire or an explosion inside the dust collector. Bonding and grounding
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.